Key Points for Daily Maintenance of Control Valves in Operation: Have You Paid Attention to These Details?
In industrial production and control processes, control valves, as core execution units, are hailed as "the hands and feet of industrial automation production lines." Their stability directly affects the smooth operation of the entire process system. Today, [Wuzhong Zhongchuang Zikong Valve] will share with you some insights on the maintenance and upkeep of control valves in daily production.
1. Daily Inspections: Essential Checks That Cannot Be Overlooked
In many cases, problems with control valves are not sudden failures, but rather the result of accumulated daily negligence. Therefore, establishing routine inspections is crucial.
Check Operation and Indication: In daily work, pay attention to whether the control valve operates smoothly, and whether there is any abnormal noise or significant vibration. At the same time, verify that the valve position indicator matches the output of the control room regulator. If a significant deviation is found between the two, it is often an early signal of valve stem sticking or a problem with the positioner feedback system-.
Focus on Sealing and Accessories: For control valves with positioners, regularly check whether the air source pressure and signal pressure are normal; for valves using graphite-asbestos packing, lubricating oil should be replenished at the packing gland approximately every three months to ensure flexible valve stem movement-. If the packing gland is found to be compressed too low or the PTFE packing has hardened, replenish or replace the packing promptly to prevent medium leakage-.
External Hazards: Regularly check whether there is rust, welding slag, or debris accumulation in the pipeline. Once these contaminants enter the valve body, they will directly cause wear of the valve core and valve seat, affecting regulation accuracy in minor cases, or causing the valve to seize in severe cases-. In dusty or corrosive environments, protective measures (such as dust covers or anti-corrosion bags) should be added around the valve stem to prevent particles or corrosive gases from entering the packing gland and guiding parts-.
2. Regular Maintenance: The "Secret" to Equipment Longevity
If superior quality injects a healthy "physique" into the control valve, then regular maintenance is the "secret" that keeps it continuously vigorous.
Cleaning and Lubrication: It is recommended to clean the control valve quarterly or semi-annually to remove accumulated oil stains and corrosion products from the surface-. At the same time, perform lubrication maintenance on moving parts such as valve stems and guide sleeves, but be careful to select lubricants compatible with the medium to avoid diaphragm aging or seal failure caused by improper lubrication-.
Seal Inspection and Replacement: Seals are the first line of defense against control valve leakage. During maintenance, inspect key sealing areas such as packing and valve seat sealing surfaces for aging or wear-. Once excessive leakage or hardened packing is found, replace it promptly and readjust the tightening force to avoid external leakage caused by insufficient tightness or increased valve stem friction due to excessive tightness.
Tightening Connection Components: For control valves in outdoor or vibration environments, regularly check whether connecting bolts are loose to ensure uniform force distribution on flange connection gaskets and prevent seal failure caused by vibration-.
III. Common Fault Troubleshooting: Solving Problems "in the Bud"
Even with proper daily maintenance, control valves may still experience some common issues after prolonged operation. Mastering basic troubleshooting methods can greatly reduce fault downtime.
Sticking Issues: When you notice significant flow fluctuations despite unchanged valve opening, it's likely that the valve core is stuck by debris. You can quickly open or close the valve fully several times to flush out the blockage using the medium's own flow. If this doesn't resolve the issue, under safe conditions, use a pipe wrench to clamp the valve stem and, with the assistance of external signal pressure, rotate the valve stem forward and backward to move the valve core past the stuck position-.
Excessive Leakage: If internal leakage is excessive, it's mostly caused by poor fit between valve core and seat or worn sealing surfaces. Disassemble and inspect whether the sealing line between valve core and seat has scratches or corrosion-. If external leakage is obvious, check whether the packing has aged or if the valve stem and packing gland are loose; readjusting or replacing the packing will resolve the issue-.
Abnormal Action or Oscillation: If the control valve experiences "won't open," "won't close tight," or constant-amplitude oscillation, it's recommended to first check whether the air source supply pressure is stable. For air-to-close valves that won't close tight, try appropriately increasing air source pressure or reducing spring preload; for air-to-open valves that won't close tight, increase the spring preload-. Additionally, check whether there's water accumulation in the diaphragm head, whether the air path is blocked, and whether there's excessive friction resistance between the valve core and sleeve-.
Inflexible Valve Stem Movement: This is mostly due to packing being too tight, bent valve stem, or debris entering the guide area. Inspect each item systematically during shutdown, disassemble and clean, and replace damaged components.
4. Precautions for Long-Term Shutdown and Restart
When the system requires a long-term shutdown, do not simply close the valve and leave it. It is recommended to clean the control valve before shutdown to remove corrosive media remaining in the valve body, and apply anti-rust grease to exposed moving parts such as the valve stem to prevent seizure caused by rust due to long-term standing.
Before resuming operation, the tightening of each connection should be re-inspected, and a full-stroke manual or automatic action test should be performed on the valve under low-load conditions to confirm that the movement is flexible and free of jamming before putting it into normal production.
Focus on Mid-to-High-End Control Valves, Providing Reliable Guarantee for the Industry
The above maintenance experience embodies the insights we have gained from serving frontline customers in the fields of power, petroleum, chemical, coal chemical, metallurgy and other industries for a long time-. Since its establishment in 2006, Wuzhong Zhongchuang Zikong Valve Co., Ltd. has been committed to the R&D, manufacturing and maintenance services of high-end control valves. Its products cover multiple series including high pressure differential control valves for severe service conditions, special power plant valves, as well as globe valves, gate valves, ball valves, butterfly valves and more-.
We deeply understand that for on-site production, even a minor jam in a control valve may affect the stable operation of the entire production line. To this end, the company not only continuously refines product quality at the manufacturing end, but also provides customers with one-stop technical services from valve maintenance to petrochemical engineering maintenance-
If you have any questions regarding the use or maintenance of control valves, please feel free to contact us for discussion. Making every valve with care and serving every customer with care is our unchanging original intention.